- Specifications
- Downloads
- Applications
- Field Pictures
- Accessories
Environmental:
Operating Temp: -76°F to +185°F (-60°C to +85°C)
Storage Temp: -76°F to +185°F (-60°C to +85°C)
Humidity: 0 to 100% RH non-condensing
Enclosure:
- Dimensions: 4” Dia x 8” L (inches) / 100 mm Dia x 200 mm
- Material: Copper-free aluminum or 316 stainless steel
- Entry size: 3/4 inch NPT or M25
- Weight: Aluminum 5.5 lbs (2.5 Kg), Stainless steel 13.2 lbs (6 Kg)
Field of View: 90° horizontal by 90° vertical
Outputs:
- Relay contacts: SPST 2A at 30Vdc for alarm and fault
- 0-20mA, HART®: 7
Speed of Response: 2-5 seconds (Typical) at 40 m (131 feet)
Flame Sensitivity Table:
| Fuel | Fire Size | Distance |
|---|---|---|
| High sensitivity | ||
| Hydrogen | 0.9m (36 inch) plume | 40m (131 feet) |
| Methylated Spirits | 0.3m x 0.3m (1ft²) | 20m (65 feet) |
| Methanol | 0.3m x 0.3m (1ft²) | 20m (65 feet) |
| n-Heptane | 0.3m x 0.3m (1ft²) | 12m (40 feet) |
| Methane | 0.9m (36 inch) plume | 30m (100 feet) |
| Document | Download |
|---|---|
| Data Sheet | Download |
Certification:
Class 1 Div 1 Groups B, C, D T4
Ambient –50°C to +85°C
Class 1 Zone 1 AEx/Ex db IIC T4
Ambient –50°C to +85°C
ATEX II 2 G Ex db IIC T4
IECEx Ex db IIC T4
Ambient –60°C to +85°C
INMETRO Ex db IIC T4*
PESO Ex db IIC T4*
Ta= -60°C to +85°C
*pending
Performance Approvals:
FM 3260
EN 54-10
Ingress:
NEMA type 6P / IP67
Safety:
IEC 61508 Certified SIL 2 Capable
Typical applications include:
- Petroleum refining
- Semiconductor manufacturing
- Aerospace applications
- Fertilizer production
- Pharmaceuticals
- Hydrogen Compressors
- Hydrogen Fueling Stations
- Hydrogen Trains / Buses
- Hydrogen Ferries
- Hydrogen to Methane Production
- Refrigeration
- Gas Plants
- Hydrogen Generators
Coming Soon!
- Flame simulator (FS301) Sunshield
- 2”, 3” & 4” Pole mount bracket
- Duct Mount Bracket
- Retrofit mounting bracket
- Air Shield
- Marine mounting bracket
- Detector Sealing Kit