| Specifications |
Dimension: - 187×147×145 mm (W×H×D), Mounting hole 138×138 mm
|
Screen: - 7-inch color touch LCD, 800×480 px
|
Channel: - Up to 32 universal analog inputs
|
Accuracy: |
Sampling Period: |
Alarm: - Up to 16 relays (normally open), 250VAC 3A / 30VDC 3A (resistive load)
|
Transmitter: - Up to 8 outputs, 4–20 mA, load ≤750Ω, Accuracy: 0.2%
|
24VDC Output: - 2 × 24VDC±10% (≤120 mA total)
|
RS485: - Standard Modbus RTU protocol
|
Ethernet: - 10/100Base-T RJ45, Modbus TCP (≤3 connections)
|
USB: - USB 2.0, supports up to 32GB USB stick
|
Micro Printer: |
Power Supply: - 100–240VAC 50Hz / DC 24VDC±10%
- Reverse protection, ≤20W
|
Preheating Time: |
Work Environment: - -10 to +60℃
- 0–85% RH (no condensation)
|
EFT: - Power: 2000V
- Signal: 1000V
|
ESD: |
Withstand Voltage: - AC220V: 1500V (terminal to ground)
- DC24V: 500V (terminal to ground)
- 1000V between isolated terminals
|
Insulation Resistance: - AC: 500V → 20MΩ
- DC: 100V → 5MΩ
|
Recording Interval: - 1s, 2s, 5s, 10s, 15s, 30s, 1min, 2min, 5min, 10min, 30min, 1h
|
Data Memory: |
Recording Duration: - 32-channel, 1-sec interval → 10 days
- Dynamic cyclic overwrite
|
Other Records: - 256 alarms, power logs, operation logs (circular storage)
|
Installation: - Indoor panel mount, IP65 rated
|