Digital flow totalizer for panel mount, measuring instant and total flow. Accepts impulse signal types NPN, PNP, pick-up, mVac, reed switch, mechanical contact, push-pull and others. Standard 96 x 48 mm(1/8 DIN) size. Scalable reading with 6 digits (‘999999’ to ‘-199999’)and configurable decimal point. Provides excitation voltage +15 Vdc(@50 mA). ‘Fast access’ function to alarm setpoints and preset value, reset function for total flow by rear contact and / or front key, rear con-tact to switch reading values, ‘Eco’ mode for reduced consumption, 5brightness levels. Single universal power supply 18 to 265 Vac/dc. Optional relays, analog output and Modbus RTU serial communications. Recommended for OEM application

Key Benefits

  • • 18 to 265 VAC/DC (50/60Hz)
  • • 15 refreshs per second
  • • 4.4 KOhms with pull-up, pull-down resistances 120 KOhms without resistances
Specifications

Digits:

  • 6

Reading:

  • 999999 / -199999

Decimal Point:

  • Configurable

LED Color:

  • Red

Digit Height:

  • 14 mm

Accepted Signal:

  • NPN, PNP, pick-up*, push-pull, reed contact, mechanical contact
  • *Minimum 10 mVac RMS

Frequency Range:

  • Max: 500 Hz
  • Min: 0.06 Hz (Gate = 16s)

Max Voltage at Input:

  • ±30 Vdc

Input Impedance:

  • 4.4 KOhms (with resistances)
  • 120 KOhms (without resistances)

Quartz Accuracy:

  • ±0.01 %

Thermal Stability:

  • 20 ppm/ºC

Excitation Voltage:

  • +15 Vdc (max. 50 mA)

Value Refresh:

  • Each impulse detected

Display Refresh:

  • 15 refresh / second

Memory Retention:

  • Yes, retains total flow value on power loss

Configuration:

  • Front keypad

Power ‘U’:

  • 18 to 265 Vac/dc (50 / 60 Hz), isolated 1500 Veff @60s

Power Wiring:

  • 1 mm² to 2.5 mm² (AWG17 to AWG14)

Output & Control Options:

  • 1 or 2 relays
  • 1 analog output 4/20 mA isolated
  • 1 Modbus RTU port, isolated

Front Protection:

  • IP65

Consumption:

  • Normal mode: <1.0 W (meter only), <2.5 W (with options)
  • Eco mode: <0.3 W (meter only), <1.5 W (with options)

Connections:

  • Plug-in screw terminals

Mount:

  • Panel

Weight:

  • <150 grams

Housing Material:

  • ABS, polycarbonate

Operating Temperature:

  • 0 to 50 ºC

Storage Temperature:

  • -20 to 70 ºC

Warm-up Time:

  • 15 minutes

Packaging:

  • 120 x 114 x 51 cm carton box

Material Included:

  • 1 x instrument C60-FL-U
  • 1 x signal terminal
  • 1 x power terminal
  • 1 x set of units
  • 1 x ‘Quick installation guide’